JetI/O 6520 |
| V81 Brochure |
Analog Input |
Thermocouple Input |
RTD Input |
Analog Output |
| Analog Input |
|
|
|
|
| Channel |
8 |
8 |
4 |
N/A |
| Resolution |
16 bits |
16 bits |
16 bits |
N/A |
| Input Range |
±10V, ±5V, ±1V, ±500mV,±150mV,
±20mA |
Type K/J/N/C/E/B/T/R
/S Thermocouple; ±2.5V, ±1V, ±500mV, ±100mV, ±50mV, ±15mV |
RTD: PT100, NI120
NTC 2.2,NTC10, NTC10-KB |
N/A |
| Acuracy |
±0.05% of FSR ±1LSB |
±0.05% of FSR ±1LSB |
±0.05% of FSR ±1LSB |
N/A |
| Sample Rate |
10 samples/sec |
10 samples/sec |
10 samples/sec |
N/A |
| Isolation |
|
2500Vrms |
|
N/A |
| Analog Output |
|
|
|
|
| Channel |
N/A |
N/A |
N/A |
4 |
| Resolution |
N/A |
N/A |
N/A |
12 bits |
| Output Range |
N/A |
N/A |
N/A |
Voltage(Source): 0-10V, ±10V. Current(Sink):
0-20mA |
|
|
| Acuracy |
N/A |
N/A |
N/A |
|
| Isolation |
|
N/A |
|
|
| Configuration |
|
|
|
|
Windows Utility |
Block I/O Configuration, Device Finder
|
| OPC Server |
OPC Server Driver, OPC Server Utility
|
Modbus/TCP |
|
| Others |
TCP/IP, UDP, SNMP, HTTP, DHCP, TFTP Upgrade, Example code
|
| Active Alarm |
|
|
|
|
| Events |
|
High/Low Temprature High/Low Vol./Current |
|
|
| Types |
|
SNMP Trap, 4 Trap
Server |
|
|
| Mechanical |
|
|
|
|
| Dimension (mm) |
120 (H) x 55 (W) x 75 (D) |
| Mounting |
DIN Rail Mount |
| Material |
Aluminum |
| Operating Temperature |
-25 ~ 70°C |
| |
|
| |
 |
| |
JetI/O 6550 |
|
|
| Digital Input |
|
|
|
|
| Channel |
14 |
| Input Type |
source |
| Input Mode |
DI/Event Counter |
| DC Input |
Logic 1: 30Vmax
Logic 0: 0-4V |
| Responding Time |
<2ms |
| Isolation |
|
| Digital Output |
|
|
|
|
| Channel |
8 |
| Input Type |
SSR, Sink |
| Input Mode |
DO or Pulse Output |
| Driving Capacity |
5-40V range,
250mA max |
| Responding Time |
|
| Isolation |
2500Vrms |
| Configuration |
|
|
|
|
Windows Utility |
Block I/O Configuration,
Device Finder
|
| OPC Server |
OPC Server Driver,
OPC Server Utili
|
Modbus/TCP |
|
| Others |
TCP/IP, UDP, SNMP, HTTP,
DHCP, TFTP Upgrade,
Example code
|
| Logic Rule |
|
|
|
|
| Conditions (IF) |
DI 0 - DI 13,
Counter 0 - Counter 13
|
| Actions (Then) |
DO 0 - DO 7 Pulse
Output 0-7 Counter
Reset SNMP Trap
|
| Mechanical |
|
|
|
|
| Dimension (mm) |
120 (H) x 55 (W) x 75 (D) |
| Mounting |
DIN Rail Mount |
| Material |
Aluminum |
| Operating Temperature |
|
| |
|
|
| |